(E.g. two 14 AWG wires have about the same cross-sectional area as a single 11 AWG wire.) This doubles the conductance. When the diameter of a solid round wire is doubled, the AWG will decrease by 6. (E.g. 1 mm diameter wire is ~18 AWG, 2 mm diameter wire is ~12 AWG, and 4 mm diameter wire is ~6 AWG).
Each diameter was multiplied by 0.890526 to give the next lower size. This is now the American wire gauge (AWG), and is prevalent in North America and used to some extent in over 65 countries, with a market share of about 30% of all power and control wires and cables. [3]
Comparison of SWG (red), AWG (blue) and IEC 60228 (black) wire gauge sizes from 0.03 to 200 mm² to scale on a 1 mm grid – in the SVG file, hover over a size to highlight it. In engineering applications, it is often most convenient to describe a wire in terms of its cross-section area, rather than its diameter, because the cross section is directly proportional to its strength and weight ...
The ampacity of a conductor, that is, the amount of current it can carry, is related to its electrical resistance: a lower-resistance conductor can carry a larger value of current. The resistance, in turn, is determined by the material the conductor is made from (as described above) and the conductor's size.
In both those instances the white wire should be identified as being hot, usually with black tape inside junction boxes. The neutral wire is identified by gray or white insulated wire, perhaps using stripes or markings. With lamp cord wire the ribbed wire is the neutral, and the smooth wire is the hot. NEC 2008 400.22(f) allows surface marking ...
For example, the United States National Electrical Code, Table 310.15(B)(16), specifies that up to three 8 AWG copper wires having a common insulating material (THWN) in a raceway, cable, or direct burial has an ampacity of 50 A when the ambient air is 30 °C, the conductor surface temperature allowed to be 75 °C. A single insulated conductor ...
Also, the size of the aluminum wire needs to be larger compared to copper wire used for the same circuit due to the increased resistance of the aluminum alloys. For example, a 15 A branch circuit supplying standard lighting fixtures can be installed with either #14 AWG copper building wire or #12 AWG aluminum building wire according to the NEC ...
For instance, instead of 14 AWG (American wire gauge) copper wire, aluminium wiring would need to be 12 AWG on a typical 15 ampere lighting circuit, though local building codes vary. Solid aluminium conductors were originally made in the 1960s from a utility-grade aluminium alloy that had undesirable properties for a building wire, and were ...