The head loss Δh (or h f) expresses the pressure loss due to friction in terms of the equivalent height of a column of the working fluid, so the pressure drop is =, where: Δh = The head loss due to pipe friction over the given length of pipe (SI units: m); [b]
h f = head loss in meters (water) over the length of pipe; L = length of pipe in meters; Q = volumetric flow rate, m 3 /s (cubic meters per second) C = pipe roughness coefficient; d = inside pipe diameter, m (meters) Note: pressure drop can be computed from head loss as h f × the unit weight of water (e.g., 9810 N/m 3 at 4 deg C)
Once the friction factors of the pipes are obtained (or calculated from pipe friction laws such as the Darcy-Weisbach equation), we can consider how to calculate the flow rates and head losses on the network. Generally the head losses (potential differences) at each node are neglected, and a solution is sought for the steady-state flows on the ...
After both minor losses and friction losses have been calculated, these values can be summed to find the total head loss. Equation for total head loss, , can be simplified and rewritten as: = [() + (,)] [5] = Frictional head loss = Downstream velocity = Gravity of Earth
The Reynolds number Re is taken to be Re = V D / ν, where V is the mean velocity of fluid flow, D is the pipe diameter, and where ν is the kinematic viscosity μ / ρ, with μ the fluid's Dynamic viscosity, and ρ the fluid's density. The pipe's relative roughness ε / D, where ε is the pipe's effective roughness height and D the pipe ...
The method also assumes that the relation between flow rate and head loss is known, but the method does not require any particular relation to be used. [1] In the case of water flow through pipes, a number of methods have been developed to determine the relationship between head loss and flow.
Pressure head is the difference in pressure between the suction point and the discharge point, expressed as an equivalent height of fluid. Velocity head represents the kinetic energy of the fluid due to its bulk motion. Friction loss (or head loss) represents energy lost to friction as fluid flows through the pipe.
where h f is the head loss due to friction, calculated from: the ratio of the length to diameter of the pipe L/D, the velocity of the flow V, and two empirical factors a and b to account for friction. This equation has been supplanted in modern hydraulics by the Darcy–Weisbach equation, which used it as a starting point.