The thermowell protects the instrument from the pressure, flow-induced forces, and chemical effects of the process fluid. Typically a thermowell is made from metal bar stock. The end of the thermowell may be of reduced diameter (as is the case with a tapered or stepped-shank thermowell) to improve the speed of response.
Hydrogen in the atmosphere is the usual cause of green rot. At high temperatures, it can diffuse through solid metals or an intact metal thermowell. Even a sheath of magnesium oxide insulating the thermocouple will not keep the hydrogen out. [15] Green rot does not occur in atmospheres sufficiently rich in oxygen, or oxygen-free.
A standard RTD sheath is 3.175 to 6.35 mm (0.1250 to 0.2500 in) in diameter; sheath diameters for thermocouples can be less than 1.6 mm (0.063 in). Accuracy and stability requirements If a tolerance of 2 °C is acceptable and the highest level of repeatability is not required, a thermocouple will serve.
The American Society of Mechanical Engineers (ASME) has developed two separate and distinct standards on temperature Measurement, B40.200 and PTC 19.3. B40.200 provides guidelines for bimetallic-actuated, filled-system, and liquid-in-glass thermometers. It also provides guidelines for thermowells. PTC 19.3 provides guidelines for temperature ...
An alternative to the Pirani gauge is the thermocouple gauge, which works on the same principle of detecting thermal conductivity of the gas by a change in temperature. In the thermocouple gauge, the temperature is sensed by a thermocouple rather than by the change in resistance of the heated wire.
Thermocouples can be connected in series as thermocouple pairs with a junction located on either side of a thermal resistance layer. The output from the thermocouple pair will be a voltage directly proportional to the temperature difference across the thermal resistance layer and also to the heat flux through the thermal resistance layer.