In vector control, an AC induction or synchronous motor is controlled under all operating conditions like a separately excited DC motor. [21] That is, the AC motor behaves like a DC motor in which the field flux linkage and armature flux linkage created by the respective field and armature (or torque component) currents are orthogonally aligned such that, when torque is controlled, the field ...
Since the 1980s, power electronics technology has reduced VFD cost and size and has improved performance through advances in semiconductor switching devices, drive topologies, simulation and control techniques, and control hardware and software. VFDs include low- and medium-voltage AC–AC and DC–AC topologies.
Direct torque control (DTC) is one method used in variable-frequency drives to control the torque (and thus finally the speed) of three-phase AC electric motors. This involves calculating an estimate of the motor's magnetic flux and torque based on the measured voltage and current of the motor.
A variable frequency drive (VFD) or variable speed drive (VSD) describes the electronic portion of the system that controls the speed of the motor. More generally, the term drive, describes equipment used to control the speed of machinery. Many industrial processes such as assembly lines must operate at different speeds for different products.
A permanent magnet synchronous motor and reluctance motor requires a control system for operating (VFD or servo drive). There is a large number of control methods for synchronous machines, selected depending on the construction of the electric motor and the scope. Control methods can be divided into: [21] [22] Scalar control. V/f control ...
A motor controller is a device or group of devices that can coordinate in a predetermined manner the performance of an electric motor. [1] A motor controller might include a manual or automatic means for starting and stopping the motor, selecting forward or reverse rotation, selecting and regulating the speed, regulating or limiting the torque, and protecting against overloads and electrical ...
The scalar control has been to a large degree replaced in high-performance motors by vector control that enables better handling of the transient processes. [1] Low cost and simplicity keeps the scalar control in the majority of low-performance motors, despite inferiority of its dynamic performance; [ 3 ] vector control is expected to become ...
The average output voltage can be controlled by different techniques namely: Pulse-width modulation; Frequency modulation; Variable frequency, variable pulse width; CLC control; In pulse-width modulation the switches are turned on at a constant chopping frequency. The total time period of one cycle of output waveform is constant.