The task of additional reactive power compensation (also known as voltage compensation) is assigned to compensating devices: [7] passive (either permanently connected or switched) sinks of reactive power (e.g., shunt reactors that are similar to transformers in construction, with a single winding and iron core [9]).
In Electrical Engineering, a static VAR compensator (SVC) is a set of electrical devices for providing fast-acting reactive power on high-voltage electricity transmission networks. [1] [2] SVCs are part of the flexible AC transmission system [3] [4] device family, regulating voltage, power factor, harmonics and stabilizing the system. A static ...
The STATCOM also provides better reactive power support at low AC voltages than an SVC, since the reactive power from a STATCOM decreases linearly with the AC voltage (the current can be maintained at the rated value even down to low AC voltage), as opposed to power being a function of a square of voltage for SVC. [38]
This can lead to a relatively cost-effective solution where the SVC only requires capacitive reactive power, although a disadvantage is that the reactive power output can only be varied in steps. Continuously variable reactive power output is only possible where the SVC contains a TCR or another variable element such as a STATCOM .
The reactive power produced by a capacitor bank is in direct proportion to the square of its terminal voltage, and if the system voltage decreases, the capacitors produce less reactive power, when it is most needed, [2] while if the system voltage increases the capacitors produce more reactive power, which exacerbates the problem. In contrast ...
The most common shunt compensation device is the Static VAR Compensator (SVC). [14] SVCs use power electronics, generally Thyristors, to switch fixed capacitors and reactors. These are referred to as Thyristor Switched Capacitor (TSC) and Thyristor Switched Reactor (TSR), respectively.
In practice, the prime mover (a power source that drives the generator) is designed for less active power than the generator is capable of (due to the fact that in real life generator always has to deliver some reactive power [2]), so a prime mover limit (a vertical dashed line on the illustration) changes the constraints somewhat (in the ...
The real power and voltage are specified for buses that are generators. These buses have a constant power generation, controlled through a prime mover, and a constant bus voltage. Slack bus – to balance the active and reactive power in the system. It is also known as the Reference Bus or the Swing Bus. The slack bus will serve as an angular ...