Search results
Results from the WOW.Com Content Network
A ground conductor only carries significant current if there is a circuit fault that would otherwise energize exposed conductive parts and present a shock hazard. In that case, circuit protection devices may detect a fault to a grounded metal enclosure and automatically de-energize the circuit, or may provide a warning of a ground fault.
In transmission line faults, roughly 5% - 10% are asymmetric line-to-line faults. [2] line-to-ground fault - a short circuit between one line and ground, very often caused by physical contact, for example due to lightning or other storm damage. In transmission line faults, roughly 65% - 70% are asymmetric line-to-ground faults. [2]
Hot is any line or neutral conductor (wire or otherwise) connected with an electrical system that has electric potential relative to electrical ground or line to neutral. Ground is a safety conductor with a low impedance path to earth. It is often called the "ground wire," or safety ground. It is either bare or has green insulation. [1]
A ground fault protection relay must trip the breaker to protect the circuit before overheating of the resistor occurs. High-resistance grounding (HRG) systems use an NGR to limit the fault current to 25 A or less. They have a continuous rating, and are designed to operate with a single-ground fault.
Each phase of the circuit is run in a separate grounded metal enclosure. The only fault possible is a phase-to-ground fault, since the enclosures are separated. This type of bus can be rated up to 50,000 amperes and up to hundreds of kilovolts (during normal service, not just for faults), but is not used for building wiring in the conventional ...
AS/NZS 3000 Wiring Rules define "extra low voltage" as "Not exceeding 50 V AC or 120 V ripple-free DC" However, AS/ACIF S009 Clause 3.1.78.1 Extra-Low Voltage (ELV)states: "a voltage not exceeding 42.4 V peak or 60 V DC [AS/NZS 60950.1:2003]" and adds a note: "This definition differs from the ELV definition contained in AS/NZS 3000:2000" which ...
This type of service is usually supplied using 240 V line-to-line and 120 V line-to-neutral. In some ways, the high leg delta service provides the best of both worlds: a line-to-line voltage that is higher than the usual 208 V that most three-phase services have, and a line-to-neutral voltage (on two of the phases) sufficient for connecting ...
When current flows from a line conductor to an earth wire, as is the case when a line conductor makes contact with an earthed surface in a Class I appliance, an automatic disconnection of supply (ADS) device such as a circuit breaker or a residual-current device (RCD) will automatically open the circuit to clear the fault. [8]