The prospective short-circuit current (PSCC), available fault current, or short-circuit making current is the highest electric current which can exist in a particular electrical system under short-circuit conditions. It is determined by the voltage and impedance of the supply system.
Calculation of the required breaking capacity involves determining the supply impedance and voltage. Supply impedance is calculated from the impedance of the elements making up the supply system. Customers of an electrical supply utility can request the maximum value of prospective short-circuit current available at their point of supply.
The solution results in voltages and currents that exist as symmetrical components; these must be transformed back into phase values by using the A matrix. Analysis of the prospective short-circuit current is required for selection of protective devices such as fuses and circuit breakers. If a circuit is to be properly protected, the fault ...
SCMVA is defined as a product of the voltage before the 3LG fault and the current that would flow after the fault (this worst-case combination will not happen in practice, but provides a useful estimation of the capacity of the circuit). SCMVA is also called a short circuit level (SCL), [3] although sometimes the term SCL is used to designate ...
A short circuit is an abnormal connection between two nodes of an electric circuit intended to be at different voltages. This results in an electric current limited only by the Thévenin equivalent resistance of the rest of the network which can cause circuit damage, overheating, fire or explosion.
Strand’s preferred alternative is to stay in contact with community church leaders about potential players and to reach out to applicants to FLBC to gauge their interest in playing basketball.
A current limiting reactor is used when the prospective short-circuit current in a distribution or transmission system is calculated to exceed the interrupting rating of the associated switchgear. The inductive reactance is chosen to be low enough for an acceptable voltage drop during normal operation, but high enough to restrict a short ...