Synchronous impedance curve (short-circuit characteristic curve), showing armature current as function of field current. The curve is obtained by rotating the generator at the rated RPM with the output terminals shorted and the output current going to 100% of the rated for the device (higher values are typically not tested to avoid overheating).
A diagram with multiple synchronous machine curves; open-circuit saturation curve is the leftmost one The open-circuit saturation curve (also open-circuit characteristic, OCC) of a synchronous generator is a plot of the output open circuit voltage as a function of the excitation current or field.
A permanent magnet synchronous generator is a generator where the excitation field is provided by a permanent magnet instead of a coil. The term synchronous refers here to the fact that the rotor and magnetic field rotate with the same speed, because the magnetic field is generated through a shaft-mounted permanent magnet mechanism, and current is induced into the stationary armature.
The generator is brought up to approximate synchronous speed by supplying more energy to its shaft - for example, opening the valves on a steam turbine, opening the gates on a hydraulic turbine, or increasing the fuel rack setting on a diesel engine. The field of the generator is energized and the voltage at the terminals of the generator is ...
In a synchronous generator, [1] the short circuit ratio is the ratio of field current required to produce rated armature voltage at the open circuit to the field current required to produce the rated armature current at short circuit. [1] [2] This ratio can also be expressed as an inverse of the saturated [3] direct-axis synchronous reactance ...
Due to high cost of a generator, a set of sensors and limiters will trigger the alarm when the generator approaches the capability-set boundary and, if no action is taken by the operator, will disconnect the generator from the grid. [3] D-curve expands with cooling. The D-curve for a particular generator can be expanded by improved cooling.
Droop speed control is a control mode used for AC electrical power generators, whereby the power output of a generator reduces as the line frequency increases. It is commonly used as the speed control mode of the governor of a prime mover driving a synchronous generator connected to an electrical grid. It works by controlling the rate of power ...
An example of synchroscope operation on a hydroelectric generator. Synchroscopes are used in any power plant that connects to an outside electrical grid and also in isolated plants containing more than one generator. Each generator must be synchronized with the others before being connected to the plant bus. If line voltages are unequal when ...